Galil Motion Control note 1222 Page 2
The DMC-1425/3425 have jumpers that must be configured properly for correct
operation. These jumpers are set at the factory but it is advisable to confirm jumper
settings before initial use.
DMC-1425/3425:
Both JP3 jumpers to MC
JP2 SMX jumper off
DMC-1425/3425-XSTEP:
Both JP3 jumpers to SD
JP2 SMX jumper on
DMC-1425/3425-STEPPER: Both JP3 jumpers to SD
JP2 SMX jumper on
When using the ICM-1460 and ICM-1460-STEPPER with the DMC-1425/3425
(and DMC-1415/3415), terminal 5 PULSE/AI1 and terminal 6 DIR/AI2 are
analog inputs only; these terminals have no stepper pulse and direction function.
When using the ICM-1460 with the DMC-1410/11/12/17, terminal 5 PULSE/AI1 and
terminal 6 DIR/AI2 provide pulse and direction for the x-axis; there are no analog
inputs on these controllers.
If the AMPEN (amp enable) and/or ERROR signals are needed for your
application, please consult Galil for alternate solutions.
If you have any questions regarding these options or their implementation, please
contact Galil's applications engineering team at support@galilmc.com or 800-377-
6329.